Home >> TECHNOLOGY

Featured Product

  • HVTF2 AC Resonant Hipot Test System for Substation Equipment

    MORE
  • HVTFW PD-free AC Series Resonant Test System

    MORE
  • HVYDQW Series Gas Type HV Testing Transformer for PD Test

    MORE
  • HVIG Impulse Voltage Generator-Marx Generator

    MORE

Tech: CT Volt-Ampere Characteristic Test And 10% Error Curve Verification2024-08-31


  Tech: CT Volt-Ampere Characteristic Test And 10% Error Curve Verification



1 Concept of CT volt-ampere characteristics

  CT volt-ampere characteristics refer to the relationship curve between the excitation current on the secondary side of the current transformer and the voltage applied on the secondary side of the current transformer when the primary side of the current transformer is open circuit (voltage is the ordinate, current is the abscissa) ), which is actually the magnetization curve of the iron core.


HVHG-F CTPT Comprehensive Transformer TesterHVFA-D CT PT TesterHVCT-1000P CT/PT Analyzer



2 Purpose of CT volt-ampere characteristic test

  (1) Check the core quality of newly put into production transformers and leave the original experimental data of CT.


  (2) During outage inspection and maintenance of CT, by identifying the saturation  degree of CT volt-ampere characteristics, that is, the position of the voltage inflection point, it is possible to determine whether there are defects such as inter-turn short circuits in the windings of the transformer after a certain period of operation, so as to promptly discover equipment defects and ensure equipment safety run.


  (3) Make a CT10% error curve based on the CT volt-ampere characteristics to verify the CT accuracy.


 More information: 

Project, News, Video,please kindly click the letters to view: 

Product: Category: CT PT Analyzer

Video: Relay Tester, CT PT Tester, Secondary Circuit Tester

News: Relay Tester, CT PT Tester, Secondary Circuit Tester

Project:Relay Tester, CT PT Tester, Secondary Circuit Tester     



3 CT volt-ampere characteristic test

  When comparing the measured volt-ampere characteristic curve with the factory volt-ampere characteristic curve or the latest measured volt-ampere characteristic curve, the voltage at the inflection point position should not be significantly reduced. If there is a significant decrease, check whether there is an inter-turn short circuit in the secondary winding. If the voltage at the rated frequency applied to the secondary terminal of the current transformer increases by 10%, the excitation current will increase by 50%, and the root mean square value of this voltage is called the inflection point position voltage.

Its theoretical basis: the CT core at the inflection point enters a saturated state. At this time, almost all the excitation current is lost in the heat of the core. Since the CT DC resistance R2 is related to the number of CT secondary winding turns, when the CT secondary winding turns are short-circuited , causing the DC resistance R to decrease, which is manifested in the CT volt-ampere characteristics as a significant decrease in the voltage U at the inflection point (when the saturation current of the CT core remains unchanged, the voltage at the inflection point U0'=I saturation × R2), according to This determines that the CT secondary winding is abnormal.

  Case analysis: Figure 1 shows the one-volt-ampere characteristic curve, in which the horizontal axis is the current I, the vertical axis is U, points A and B are the inflection points, the voltage at point B is 1600 V, the voltage at point A is 1878 V, and the voltage at point B is 1878 V. The voltage is significantly lower than the voltage at point A. Both curves are the same CT volt-ampere characteristic curve, and the upper 1 curve is the original volt-ampere characteristic curve when the CT leaves the factory, and the lower 2 curves are the latest measurement curves. According to the above analysis, it can be seen that the CT A defect exists and requires further inspection or replacement.


image.png


Figure 1 volt-ampere characteristic curve


4 CT 10% error curve verification

  The 10% error curve is an important basic characteristic of the current transformer for protection. The relay protection device reflects the fault condition of the primary system. When the primary system fails and the protection device is activated, the primary current of the current transformer is usually much larger than the current during normal operation. Therefore, the error of the current transformer will also increase. In order for the electrical protection device to correctly reflect the primary system condition and operate correctly, the current transformer ratio error is required to be less than or equal to 10%. Whether the primary current increases or the secondary load impedance increases, the result will cause the induced electromotive force of the current transformer to increase, thereby increasing the error. The so-called 10% error curve is the characteristic curve of the relationship between the ratio of the primary current (I1) to its rated current (I1N) (m = I1/ I1N) and the secondary load impedance (ZY) when the ratio error is 10%. It can also be understood as the maximum secondary load impedance allowed to make the current transformer ratio error less than or equal to 10% under different primary current multiples.


  In actual work, the volt-ampere characteristic method is often used to first measure the volt-ampere characteristic curve of the CT, and then draw the "10% error curve of the CT" based on the volt-ampere characteristic curve of the CT. According to the 10% error curve of the current transformer, the maximum allowable impedance ZYmax of the secondary circuit is obtained and compared with the actual impedance ZL of the secondary circuit. If ZL<ZYmax, it is considered that the current transformer meets the 10% error requirement.

1725112907466588.png



Figure 2 Equivalent circuit diagram of current transformer connected to load


Theoretical basis: 

The following relationship is obtained from Figure 2


E=I2×(Z2+ZY) (2)

m=I1/IN (3)

When the transformer error is 10%, the following relationship exists:

I2=9I0 (4)

I1/k=10I0 (5)

Substituting formula (4) into formula (2) yields:

ZY =E/9I0-Z2 (6)

Substituting formula (5) into formula yields:

m= I1/I1N=10I0 /5=2I0 (7)

According to the excitation characteristic E-I0 data calculated in 2) and formulas (6) and (7), the 10% error curve of the current transformer can be obtained.


Case analysis: Table 1 is the measured and calculated data of LB-220 current transformer, and its ultimate purpose is to calculate the secondary allowable load ZYmax. Figure 3 is a function curve of ZYmax and m, with a 10% error, drawn based on the data in the table. Different maximum allowable load impedances can be found for different short-circuit current multiples. Assuming that the current transformer is used at the maximum short-circuit current Ik=18kA, then m=15, and ZYmax=3.9Ω is found, which is greater than the measured secondary load of 1.96Ω. The conclusion is that it can meet the requirements.

1725113641477505.png


Figure 3 10% error curve

Table 1 Measurement and calculation of CT 10% error curve


Basic parametersPrimary rated current1200ASecondary rated current5AAccuracy level10P20
Secondary loadCurrent I5AMeasured voltage9.8VZL1.96Ω


Test itemsSymbolsData sourceValues





Excitation currentI0 (A)Measured by experiment0.5124568
Test voltageU0 (V)Measured by experiment280290298300306308310


Winding internal resistanceR2(Ω)Measured by experiment0.535
Winding leakage reactanceZ2(Ω)≈2R20.706


Internal electromotive forceE0(V)=U0-I0Z2279289296297302304304
Allowable total loadZ2+ZY=E0/9I062.132.116.58.256.725.634.22
Allowable secondary loadZY(Ω)= E0/9I0-Z261.431.415.97.556.024.923.52
Short circuit current multiplem2I01248101216